Extreme Sensors for the Most Challenging Environments.     Check out our full line of accessories to complement your photoelectric systems.     Let us help you source those hard-to-find replacement parts from Europe — we will save you time and money.     Pantron Automation is proud to be the North American distributor for Fuchs Umwelttechnik, GmbH, manufacturer of high-quality fume and particulate extraction equipment.     If you have an application that’s causing problems, let us help you solve it with high-quality industrial sensors and controls that are designed to endure the worst conditions on the planet.     Are you interested in being a distributor for Pantron? Contact our Belmont office for details.     Need proximity sensors for extremely hot or cold environments? Check out the products offered by the German manufacturer, EGE Elektronik.    
Car wash automation Sawmill automation Machine automation Fume extraction Climate and environmental monitoring Sensors for robotics Sensors for food processing Welding sensors Sensors for pharmaceutical applications Sensors for doors and gates Sensors for wastewater applications Paper and pulp sensors
ISM-1230 product image placeholder
PANTRONISM-1230/24VDC

ISM-1230

1-channel automatic amplifier for optical dust and turbidity measurement. The ISM-1230 is a one-channel amplifier for optical dust and turbidity measurement. Using modulated infrared light, it automatically adjusts transmit power so the receiver maintains a constant signal level while a 0 ... 10 V analog output tracks actual process attenuation.

Up to 55 m range0 ... 10 V analog outputTeach inputAutomatic operationAlarm output24 VDC

Key Features

  • Special amplifier for optical dust and turbidity measurement.
  • Automatic transmit-power regulation compensates for slow sensor contamination.
  • Basic transmit level selectable low or high.
  • Analog output proportional to attenuation / turbidity conditions.
  • Alarm output for power limit and teach input for setup.
  • DIN-rail package with floating switching output.

Best Fit Applications

  • Dust level monitoring in process ducts and equipment.
  • Optical turbidity measurement where media change over time.
  • Installations where sensor contamination changes slowly but process turbidity changes quickly.
  • Long-range opposed-mode monitoring with infrared sensors.

Technical Specifications

Operating voltage 24 V DC / ±20% / 2.4 W
Operating basis Modulated infrared light
Transmit frequency 3.7 kHz / 4.3 kHz
Transmit power Automatic
Basic transmit level Low / High
Reaction time 24 ms
Switching output Semiconductor relay, normally open
Output rating 100 mA / 60 V AC (DC)
Alarm output PNP, 100 mA / 24 V DC
Test input 0 ... 30 V DC
Analog output 0 ... 10 V DC
Dimensions 35.5 x 90 x 58.5 mm

Compatible Sensor Pairs and Maximum Through-Beam Range

Transmitter family With receiver IRL-... With receiver IR-... Typical use note
IT-..., ITL-... 7 m 15 m Compact standard range
IT-...HP, ITH-... 10 m 25 m Higher power sensors
ITA-... 20 m 55 m Longest stated range

Maximum range values shown are for through-beam installations using the listed Pantron transmitter and receiver families.

Ordering and Accessories

Connection / Variant Order code
Plug (screw terminals) ISM-1230/24VDC
Accessory Order code
Protective enclosure PanBox 1x1
Power supply PSU-1000S/95...265VAC

Device Notes

  • Analog output depends on sensor spacing, alignment, contamination, and actual medium turbidity.
  • With fixed sensor mounting, fast changes at the output mainly represent actual turbidity.
  • The catalog shows DIP settings for basic transmit level, transmit frequency, and measurement range.

Related Products